honeywell霍尼韦尔执行器m6284f1039-s
产品资料:
minimum load: 10 ma at 5 vdc
mechanical life: 1,000,000 operations
electrical life: make: 50,000 times, break: 30,000 times
ambient operating temperature ?20 to 60°c (with no condensation or icing)
storage temperature ?40 to 70°c (with no condensation or icing)
ambient operating humidity 25% to 85% (with no condensation)
storage humidity 25% to 85% (with no condensation)
altitude 2,000 m max.
terminal screw tightening torque 0.54 n·m
terminal wiring method
recommended wire
solid wire: 2.5 mm2
twisted wires: awg16, awg18
note: 1. ferrules with insulating sleeves must be used with twisted wires.
2. two wires can be twisted together.
recommended ferrules
al 1,5-8bk (for awg16) manufactured by phoenix contact
al 1-8rd (for awg18) manufactured by phoenix contact
al 0,75-8gy (for awg18) manufactured by phoenix contact
case color munsell 5y8/1
case material abs resin (self-extinguishing resin) ul94-v0
weight approx. 110 g
mounting mounted to din track or via m4 screws (tightening torque: 1.2 n·m)
dimensions 22.5 (w) × 90 (h) × 100 (d) mm
k8ab-ph1
4
nomenclature
front
indicators
*1.the input across l1 and l3 is used for the internal power supply.
therefore, the power indicator will not be lit if there is no input
across l1 and l3.
*2.use either a solid wire of 2.5 mm2 maximum or a ferrule with
insulating sleeve for the terminal connection.
the length of the exposed current-carrying part inserted into the
terminal must be 8 mm or less to maintain dielectric strength after
connection.
recommended ferrules
phoenix contact
? al 1,5-8bk (for awg16)
? al 1-8rd (for awg18)
? al 0,75-8gy (for awg18)
*3.tightening torque
recommended: 0.54 n·m
详细介绍